Layanan penggantian CT switchyard 150kV: pengadaan CT baru sesuai spesifikasi PLN, pembongkaran CT lama, pemasangan, pengujian lengkap, dan komisioning ulang. Termasuk civl work fondasi jika diperlukan.
Kapan CT Perlu Diganti?
- CT bocor minyak pada porcelain head (oil-filled type)
- Hasil uji Tan Delta melebihi batas (deteriorasi dielektrik)
- Rasio error melebihi class accuracy (0.5P, 5P, 10P)
- SF6 pressure drop pada SF6 CT
- Partial discharge level tinggi
- CT terkena gangguan (short circuit / lightning)
Prosedur Penggantian
- Engineering: spesifikasi CT sesuai SPLN/PLN standard (ratio, burden, class, knee)
- Procurement CT baru (ABB, Siemens, Arteche, Nokian)
- Outage planning & izin kerja PLN dispatcher
- Disassembly CT lama: grounding, draining oil, de-energize
- Installation CT baru: setting level minyak, leak test
- Uji: rasio (CTA Omicron), burden, knee point, polarity
- Re-wiring secondary: relay panel, metering, SCADA
- Energize & commissioning
Spesifikasi CT yang Kami Handle
CT 150kV oil-filled (Siemens, ABB, Arteche, Prolec), SF6-insulated CT, Gas insulated CT untuk GIS. Ratio 200/1 hingga 3000/1. Class 0.2S/0.5/5P10/5P20.